HOW TO SETTING 1747-UIC

Plug in the 1747-UIC adapter of the USB port and install the 1747-UIC hardware driver according to the manual. It is best to use it under XP SP2. The driver of USB DH-485 Serial port COM3 (USB to virtual serial port) displayed in the device manager is normal No, you need to reinstall the 1747-UIC hardware driver again.
Under XP SP3, only USB Serial port COM3 may be displayed.

Start RSLINX and add DH485-UIC driver.

1747-UIC adapter DIP to DH485, docking with RJ45 port, RSLINX choose AB-UIC-1 driver to connect to SLC500 / 01.

HOW TO CONFIGURE THE 1747-UIC

1747-UIC & USB-1747-PIC Driver

Categories
CABLE DRIVE

Qc30r2

How to use Mitsubishi Usb-Qc30r2 Cable?

Mitsubishi USB-QC30R2 programming cable is emulated into a traditional serial port (commonly known as COM port) through the USB port of the computer, so that the existing various programming software, communication software and monitoring software are used. This cable is suitable for Mitsubishi Q series PLC

QC30R2 Cable Pinout

qc30r2 cable diagram
qc30r2 cable diagram

How to use USB-QC30R2

  1. USB-QC30R2 programming cable requires a USB driver to be installed (usb qc30r2 driver download)
  2. After the driver installation is completed, the COM port corresponding to the USB-QC30R2 programming cable will appear in the Windows device manager. Just select the COM port in the programming software, which is exactly the same as the serial programming cable QC30R2.
  3. When using, first insert the cable into the USB port of the computer, and then insert the 6-pin round port into the Q PLC
  4. Open-Explorer-View COM slogan by clicking with the mouse-My Computer-Control Panel-Administrative Tools-Computer Management-Device Manager-Port (COM and PT) -Prolific USB-to-SerialComm (COMx)
    This COMx is the COM port used by the USB programming cable
  5. Open the programming software GX DEVELOPER, open-online-transmission settings-and double-click-serial port (USB)-set the COM port, and set the baud rate to 9600BPS to communicate
device manager com port
Com Port
gx develop software serial port
GX DEVELOPER setting

USB QC30R2 Driver Download

Categories
CABLE DRIVE

Mitsubishi sc09 plc programming cable

Difference between Mitsubishi PLC programming cable USB-SC09 and USWhat is the difference between Mitsubishi PLC programming cable USB-SC09 and USB-SC09-FX

USB-SC09-FX is only used for Mitsubishi FX series, USB-SC09 is generally used for Mitsubishi FX series and A series

Mitsubishi plc pin interface diagram
sc09 programming cable diagram
sc09 programming cable diagram
sc09 programming cable diagram
sc09 programming cable diagram

How to use usb-sc09 cable?

The USB-SC09 programming cable requires a USB device driver to be used.
After the driver installation is complete, the COM port corresponding to the USB-SC09 programming cable will appear in the Windows device manager. Just select the COM port in the programming software or other application software. Other communication parameters use the default settings. The next use is the same as the traditional RS232 port programming cable. A
Note: DB25M plug and MD8M plug at the RS422 end cannot be used at the same time.

usb-sc09 driver free download

amsamotion usb-sc09-fx driver download

Categories
TECHNICAL

How to Use RSLOGIX 500 software

Rslogix500 is a programming tool for SLC500 series and MicroLogix controllers. here is how to use rslogix 500 software

(1) RS232 serial cable (model: 1747-CP3) connects the computer serial port and SLC serial port.
(2) Run Rslinx software

In the Rslinx software form menu, select Communications- Configure Drivers

In the Configure Drivers- Available Drivers dialog box, select Ethernet to PLC-5 or 5820-EI
Click Add new to enter the Add New Rslinx Driver dialog box.

In Add New Rslinx Driver, the device name specified by the user (generally the default is acceptable), click OK
Enter Configure Driver for Ethernet to PLC-5 or 5820-EI

In the window Configure Driver for Ethernet to PLC-5 or 5820-EI, the user must specify the IP address of the SLC in order to communicate between the Ethernet SLC and the computer. After filling in the IP address, click Accept;
Fill in the IP address of the computer, click Accept, and click OK.

Go back to Configure Drivers and see AB_ETH-1 A-B Ethernet RUNNING

Available Drivers–Select RS-232 DF1 Devices and click Add new to enter Configure Allen-Bradley DF1 Communications Device

Fill in the serial port number in Comm Port, Device must select SLC-CH0 / Micro / PanelView, and then click Auto-Configure, see Auto Configuration Successful on the right! Click OK.

Return to Configure Drivers, see AB_DF1-1 DH485 sta: 0 com1: RUNNING in the Configured Drivers, click Close.

Return to the Rslinx software and see AB_DF-1, DH-485 and AB_ETH-1, Ethernet.
The SLC5 / 05 processor in AB_DF-1, and the SLC processor in AB_ETH-1 are crossed and cannot communicate

(3) Run Rslogix500 software

In the Rslogix500 software menu, select File ——> New,
Select Processor Type, fill in the name of the processor in the Processor Name, select the communication protocol of the processor in Communication Settings ——> Driver; click Who Active (select the node address of the processor),
Rslinx Gateway, select SLC-5 / 05 in AB_DF-1, DH485 network, click OK; return to Select Processor Type, click OK, enter Rslogix500 software programming form.

Select Controller on the left side of Rslogix500 software, enter Controller Properties, reselect the model and name of the processor in the General menu, and reselect the communication protocol in the Controller Communications menu, and click OK.

Select IO Configure, click Read IO Config. (Or configure according to the I / O frame, power supply, and I / O module used by the user) to enter Read IO Configure from Online Processor

Click Read IO Config in Read IO Configuration from Online Processor. Return to I / O Configuration, see the frame and I / O module have been automatically configured

Select Channel Configuration, fill in the IP address of SLC-5 / 05 in the IP Address box of the Chan.1-System menu (must be the same as the processor IP address specified in the Rslinx software), and fill in the mask in the Subnet Mask (Generally 255 · 255 · 255 · 0), Bootp Enable empty, click Apply, and click OK.

3·16

Return to the Rslogix500 software, select Comms——Download on the menu (before Download, the SLC processor switch must be switched to Program or Test state), some dialog boxes will appear during the Download process, all answer OK or Apply. Do You want to go Online appears? Click Yes to return to programming. You can see the ladder in the menu is rotating, and the Download is successful.

Re-enter the Rslinx software, you can see that the SLC processors in the two networks are running, the network configuration is successful, unplug the RS-232 serial cable for configuration

Rslogix500 Program

Rslogix500 software has three programming modes: offline programming mode, online programming mode and simulation programming mode. They have their own advantages and disadvantages.

Offline programming

Advantages: Offline programming is very flexible, programming can be carried out at will, and is not limited by the processor. Disadvantages: the steps are cumbersome, the program cannot be debugged after the program is compiled, and the running status of the program cannot be observed.

(1) Create a new document
Run the Rslogix500 software, select File——New, Select Processor Type, fill in the Processor Name in the Processor Name, select the type of processor used, select the network communication in the Communication settings Driver Agreement, click OK to enter Rslogix500 software

(2) Configure the processor
Select Controller Properties in programming, you can re-select the processor name, model, network protocol, etc., and click OK when finished.

(3) Configure I / 0 module
Select I / O Configuration
Select the framework used by the user in Racks
Select the I / O module in the frame in Current Cards Available
Select the frame power supply in PowerSupply,
Close the window when finished.

(4) Configure the processor channel
Select Channel Configuration, fill in the IP address of the SLC processor in the IP Address of Chan.1-System menu (must be the same as the IP address specified by Rslinx software), the Bootp Enable option is empty, click Apply, and click OK.

(5) Program ladder diagram
Program the ladder diagram in LAD2. After editing the program, select Verify File in Edit to verify the program. If there are errors, you can modify it.

(6) Save the program
If the program is correct, select Save As in File, fill in the file name you want in File name, select RSLogix files type (* .RSS) in Save as type, click Save, the file is successfully saved.

(7) Download the program (the switch of the SLC processor must be switched to Program or Test state)

If you want to debug the program, you must download the program to the processor and perform online debugging to get the result. The download process is similar to the download process during configuration

(8) Run the program
Turn the processor switch to the Run state, and the program runs.

Online programming

Advantages: simple programming steps, online debugging and running at any time, and results can be obtained.
Disadvantages: Due to programming errors, it may cause damage to the processor, equipment or personnel.

(1) Establish an online connection
Run the Rslinx software, select Configure Driver in Communications, select the network protocol of the corresponding processor-> click Add New-> click Close, return to the Rslinx form, and see that the processor is running in the corresponding network.

(2) Create a new document
Enter New-Who Active-Rslinx Gatewag, select the corresponding processor, click OK, return to the New dialog box, and click OK.

(3) Configure the processor
The steps are similar to offline configuration, except that in the Controller Communications menu, as long as you click Who Active, the following steps are the same as step (2).

(4) Configure I / O module
Select IO Configuration-Read IO Config-Read IO Configuration Online Processor-Read IO Config-IO Configuration, you can see that the IO module has been configured.

(5) Configure the processor channel The steps are exactly the same as the offline configuration.

(6) Download empty program
The steps are exactly the same as offline download.

(7)进行在线编程

(7) Online programming
When performing online programming, the switch of the processor must be set to Test, programming in the Remote Program state, and running in the Remote Run state.

(8) Save procedure The steps are exactly the same as offline save.

Emulate programming (recommended)

Advantages: No need for SLC processor support, replace the processor with software, you can debug the program at any time without danger.
Disadvantages: Some instructions cannot be simulated, and the simulation software (current version) cannot support the SLC-5 / 05 processor.

(1) Create a simulation file
The procedure for creating a new file is the same as creating a new file by offline programming. Select Emu500-1 in the Communication Settings Driver box.
(2) Configuring the processor is the same as offline programming.
(3) Configure I / O module is the same as offline programming.
(4) Save the file
Same as offline programming, except that * .ACH must be selected when selecting Save as type.
(5) Run simulation software
Run Rsemulate500 software, open the * .ACH file saved by Rslogix500 software.

(6) Connect online
Run Rslinx software, add SLC500 (DH485) Emulator when adding network protocol. After the addition is successful, the processor icon appears on the corresponding network, and the connection is successful. (7) Online programming and running Return to the Rslogix500 programming form, click Go online to go online for online programming; click Run to run.

Categories
CABLE DRIVE

6es7972-0cb20-0xa0

6es7972-0cb20-0xa0 vs 6gk1571-0ba00-0aa0

6GK1571-0BA00-0AA0

PC adapter USB A2 USB adapter (USB V2.0) for connection of a PG/PC or notebook to SIMATIC S7 via PROFIBUS or MPI contain USB cable 5 m, MPI cable 0.3 m can be used under Windows XP/Vista/ Windows 7 32/64-bit and higher

6ES7972-0CB20-0XA0

Siemens usb-mpi s7-200/300/400 plc cable 6es7972-0cb20-0xa0

SIMATIC S7, PC ADAPTER USB F. CONNECTION OF S7-200/300/ 400, C7;
WITH USB-CABLE (5M) CAN BE USED UNDER WINXP/VISTA/ WINDOWS 7 32/64BIT

6es7972-0cb20-0xa0 manual

Use 6ES7 972-0CB20-0XA0 (PC ADAPTER USB) to download the s7-300 / 400 plc program, but the driver cannot be install?

Solution: Download PC Adapt USB driver file

Find the driver file and copy it to: C: \ Program Files \ Common Files \ Siemens \ Automation \ Simatic OAM \ Drivers

Then open “Device Manager”, select “SIMATIC PC Adaptre USB”, right-click, and select “Browse my computer for computer driver software”

Select the folder (C: \ Program Files \ Common Files \ Siemens \ Automation \ Simatic OAM \ Drivers) and click Next:

Then the driver will be installed automatically

Now the drive has been successful installation, return to the “Device Manager.” Seeing the yellow warning is gone.

6ES7 972-0CB20-0XA0(PC ADAPTER USB)

*amsamotion mpi driver is same as siemens usb to mpi driver

SIEMENS USB TO MPI(6es7-972-0cb20-0xa0) Driver Download windows 10

Categories
CABLE DRIVE

HOW TO INSTALL AMSAMOTION USB TO SERIAL DRIVER

This is the latest step-by-step instructions for installing a USB to serial cable and identifying and changing the COM port number. This applies to all Windows operating systems.

This is the latest step-by-step instructions for PLC data cable driver CH340 DRIVER, FTDI DRIVER, installing USB to serial cable, and identifying and changing COM port number.

This applies to all Windows operating systems.

The following procedure applies to all our cables, including Mitsubishi usb-sc09 usb-qc30r2, Delta usbacab230, Allen Bradley usb-1761-CBL-PM02, usb-1747-CP3, and usb-2711-NC13, etc.

To begin, find the driver suitable for the plc data line. If the steps are clear, you can view it here.

Economic version CH340 install

High speed version FT232

When you are done, open the “Device Manager” and the USB to serial adapter displays

Categories
TECHNICAL

TSXPCX3030 USB cable

The TSXPCX3030 USB cable has been replaced with the following two part numbers.

TSXCUSB485 – USB to RS485 Serial Converter
TSXCRJMD25 – RJ45 Serial to 8 pin mini DIN cable for connecting to Premium, TSX Micro and Twido programming ports.

Categories
TECHNICAL

PC-TTY WIRING DIAGRAM

PC-TTY is RS232 to Siemens S5 series PLC programming port (DB15) communication interface cable

Note: PC-TTY can’t be switched by USB-CIF31 as it only has serials port without USB.

or you can buy here

Categories
TECHNICAL

USB-SC09-FX DRIVER

USB-SC09-FX is Mitsubishi PLC Programming Cable FX0N FX1N FX2N FX0S FX1S FX3U FX3G Series Communication Cable.

USB-SC09-FX VS USB-SC09

Difference between Mitsubishi PLC programming cable USB-SC09 and USB-SC09-FX:

USB-SC09-FX is only used for Mitsubishi FX series, USB-SC09 is commonly used for Mitsubishi FX series and A series.

USB-SC09-FX Pinout

MITSUBISHI PLC round head 8 pin rs422 interface definition

the usb-sc09-fx driver support windows 7 10 64bit

Categories
TECHNICAL

USB-PPI DRIVER

you need choose right usb driver for the different version. Economic version/upgrade version/isolated version use CH340 driver,High speed communication version/Omnipotent version use FTDI driver.